Different Types of Metering Devices
The guide explains various HVAC metering devices, focusing on thermostatic expansion valves (TEVs), which regulate refrigerant flow by controlling superheat and pressure drops between system sides, detailing their components, operation, and proper sensor bulb placement for effective evaporator feeding and pressure regulation.
Different metering devices are crucial to all HVAC systems’ operation. There are several metering devices and valves governing the flow of refrigerant through these systems to help regulate pressure. This guide covers the basics about how metering devices are fitted to a line, their purpose and function, and how to identify problems with them.
Core Functions of a Metering Device
There are several metering devices in a typical system, including the thermostatic expansion valve (TEV or TXV), automatic expansion valves, electronically-governed expansion valves, balanced port TEVs, superheat and multi-circuited TEVs, and evaporators. The two basic functions of a metering device include:
- 1.Feeding refrigerant to the evaporator
- 2.Providing a pressure and temperature drop from the high side to low side
Thermostatic Expansion Valve (TEV)
The functions of a TEV include measuring and adjusting superheat and providing a place for mounting the sensing bulb. TEVs are also used on multi-circuit evaporators. The sole role of a TEV is to control the flow rate of liquid refrigerant into the evaporator. It has no control over air temperature, humidity, capacity, suction pressure, or head pressure.
Inside the TEV, you’ll find:
- Head and diaphragm
- Pins
- Needle and orifice
- Inlet screen
- Spring
- Packing gland
- Adjustment stem
The TEV is designed to respond to the temperature of refrigerant vapor as it leaves the evaporator, and to pressure in the evaporator itself (superheat).
The TEV opens with force from the bulb sensor and capillary tube (pressing on the head and diaphragm) and then closes again with pressure from the evaporator. The spring inside the TEV is usually adjustable so that a technician can modify its sensitivity to closing under evaporator pressure.
TEV Bulb Functionality
On a ⅞” suction line, the TEV bulb should be situated at 4 o’clock or 8 o’clock along the line. For lines that are smaller in diameter than ⅞”, it should be anywhere between 8 and 4, but should never be mounted at the bottom of the line. Bulbs that are mounted directly at the bottom of the line will not measure temperature accurately. The suction line will have warmer vapor on top and cold oil along the bottom.
The bulb should be mounted on a smooth section of the line (rather than a brazed joint), using stainless hose clamps. Tighten the clamps enough to ensure good thermal contact with the line, but not so tight that they deform and crush the bulb.
Ideally, the bulb should be mounted on a horizontal run of a pipe, but in a pinch it can be mounted vertically – just make sure the capillary line is pointed up and not down.
TEV Screens
The screen in a TEV is essentially a filter that traps any dirt and contaminants before they enter the valve. For TEVs that are sweat-mounted or flare-mounted, the screen is at the inlet, allowing it to be easily unscrewed, inspected, and cleaned.
Sporlan TEV Charts
TEVs need to be the right rating for the right application. Selection charts enable you to determine the right TEV according to:
- Refrigerant
- Tonnage
- Application, with the code of “C” for medium temperature, “Z” for low temperature and “ZP40” for low temperature/outlet pressure limited to 40 psig
Steps to determine the right TEV according to Sporlan charts:
- 1.Determine the temperature of liquid refrigerant entering the valve
- 2.Determine pressure drop across the valve
- 3.Select the right valve from Sporlan chart
- 4.Determine if external pressure equalizer is necessary
- 5.Select body type according to style of connections (brazed, sweat, flare mount)
- 6.Select Sporlan selective thermostatic charge
Valve Identification
To pick the right TEV for the right application, you have to be able to interpret the code that identifies the TEV. A typical valve code (printed on the valve head) might read:
R-22
SVE-2-GA
Breakdown:
- S: valve body style
- V: type of refrigerant (R-22)
- E: externally equalized
- 2: two-ton capacity
- GA: air conditioning application
Some TEVs can be used with more than one type of refrigerant, provided that evaporator temperatures and pressures are the same. Another typical valve code:
FSE 1 ZP
- F: valve body style
- S: type of refrigerant (R404A, but also compatible with 502, 402A, and 507)
- E: externally equalized
- 1: one-ton capacity
- Z: low-temperature application (freezer)
- P: pressure limiting
Understanding and Measuring Superheat
Superheat can be measured as the difference between suction line temperature and evaporator temperature.
- High superheat: The evaporator is starving for refrigerant because it is boiling off too soon (before it can make it to the evaporator).
- Low superheat: The evaporator is flooded with liquid refrigerant, which may allow liquid refrigerant to make its way back down the line to the compressor and can lead to compressor failure.
To calculate superheat:
- 1.Use a digital thermometer on the suction line, right around the TEV bulb.
- 2.Take a reading of suction pressure at the suction line’s fitting.
- 3.Refer to a table to determine the temperature for that refrigerant at that specific suction pressure.
- 4.The difference between the two temperatures is the superheat reading.
Excessive Superheat
If superheat is excessive, the technician can reduce spring pressure in the TEV, allowing more refrigerant to flow through into the evaporator. This means turning the valve stem counterclockwise, loosening the spring pressure. Adjust about ¼ turn at a time, then wait about 15 minutes for the system pressure and temperature to level off again. For an R404A system, a full turn of the stem would mean an adjustment of 4 degrees of superheat.
How to Raise Superheat
To raise superheat, increase spring pressure to reduce the flow of refrigerant through the valve into the evaporator. Turn the stem clockwise to tighten the spring. Adjust ¼ turn at a time and wait 10-15 minutes before adjusting again.
These are general rules of thumb, as specs can vary from one design of TEV to another.
Related
The Beginner's Guide to Owning an HVAC Business
The article outlines the lucrative and growing U.S. HVAC market, valued at $17.45 billion and expected to reach $26.93 billion by 2030, emphasizing the importance of a detailed business plan that defines a niche, identifies target markets, and leverages multiple revenue streams such as new installations, repairs, and maintenance to build a recession-proof HVAC business.
Online Facilities Maintenance Training
Interplay Learning offers a comprehensive, affordable, and expert-led online facilities maintenance training platform designed to quickly upskill both new and advanced technicians in areas like HVAC, electrical, and plumbing, helping organizations reduce costs, build team confidence, and improve workforce capabilities through interactive courses and proven success stories.
Four HVAC Trends Impacting the Industry: Let Training Keep You Ahead of the Curve
The HVAC industry is rapidly evolving due to technological advancements, stricter efficiency regulations, and a worsening skilled labor shortage, making comprehensive, brand-agnostic training essential for technicians to stay current with new smart systems, refrigerants, and workforce demands while addressing sustainability and regulatory challenges.
Interplay Learning Launches Hotel Maintenance Training
Interplay Learning has launched a Hospitality training catalog featuring expert-led courses and 3D simulations in HVAC, plumbing, electrical, and safety to help hotel brands and management companies streamline operations, reduce costs, and address skilled labor shortages by providing flexible, scalable, and customizable online and VR maintenance training accessible anytime on any device.
Online Skilled Trades Courses Catalog
Interplay offers a comprehensive online skilled trades course catalog with over 500 hours of structured, expert-developed training and realistic 3D simulations across categories like HVAC, plumbing, electrical, and safety, featuring learning and competency paths designed to prepare technicians for certifications such as NATE, IACET, EPA 608, and OSHA 10.
Commercial HVAC Training
Interplay Learning offers expert-led, simulation-based online commercial HVAC training combining 3D and VR technologies to rapidly develop, upskill, and retain technicians at all levels, helping companies like QuesTec Mechanical and Dual Temp create effective apprenticeship and career ladder programs that enhance workforce engagement, job readiness, and retention.